Program features 95
Miscellaneous
Backup and restore
You can make backups of the settings manually to the control panel and can restore
backup to the drive, or a new drive replacing a faulty one. You can also make
backups and restore on the panel with the Drive composer PC tool.
Backup
Manual backup
Make a backup when necessary, for example, after you have started up the drive or
when you want to copy the settings to another drive.
Parameter changes from fieldbus interfaces are ignored unless you have forced
parameter saving with parameter 96.07 Parameter save manually.
Automatic backup
The control panel has a dedicated space for one automatic backup. An automatic
backup is created two hours after the last parameter change. After completing the
backup, the panel waits for 24 hours before checking if there are additional parameter
changes. If there are, it creates a new backup overwriting the previous one when two
hours have passed after the latest change.
You cannot adjust the delay time or disable the automatic backup function.
Parameter changes from fieldbus interfaces are ignored unless you have forced
parameter saving with parameter 96.07 Parameter save manually.
Restore
The backups are shown on the panel. Automatic backups are marked with icon
and manual backups with . To restore a backup, select it and press . In the
following display you can view backup contents and restore all parameters or select a
subset to be restored.
Note: To restore a backup, the drive has to be in Local control.
Settings
Main menu
Backup data
Parameter 96.07 Parameter save manually (page 356).
User parameter sets
The drive supports four user parameter sets that can be saved to the permanent
memory and recalled using drive parameters. It is also possible to use digital inputs to
switch between user parameter sets. To change a user parameter set, the drive has
to be stopped.

Table of Contents

Other manuals for ABB ACS560

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS560 and is the answer not in the manual?

ABB ACS560 Specifications

General IconGeneral
Frequency50/60 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit
Communication InterfacesModbus RTU, Profibus DP, CANopen, Ethernet/IP
Enclosure RatingIP21
Ambient Temperature-10 to +50 °C
Input Voltage380 to 480 V AC
Cooling MethodAir cooling (natural convection or forced ventilation)

Related product manuals