Fieldbus control through a fieldbus adapter 473
Actual values
Actual values are 16-bit words containing information on the operation of the drive.
The types of the monitored signals are selected by parameters 50.07 FBA A actual 1
type and 50.08 FBA A actual 2 type.
Debugging the network words
If parameter 50.12 FBA A debug mode is set to Fast [1], the actual values sent to the
fieldbus are displayed by 50.17 FBA A actual value 1 and 50.18 FBA A actual value
2.
Scaling of actual values
The actual values are scaled as defined by parameters 46.0146.04; which scaling
is in use depends on the setting of parameters 50.07 FBA A actual 1 type and 50.08
FBA A actual 2 type.
46.01 (with speed reference)
46.02 (with frequency reference)
0
-20000
20000
DriveFieldbus
0
10000
-10000
46.03 (with torque reference)
-(46.01) (with speed reference)
-(46.02) (with frequency reference)
-(46.03) (with torque reference)

Table of Contents

Other manuals for ABB ACS560

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACS560 and is the answer not in the manual?

ABB ACS560 Specifications

General IconGeneral
Frequency50/60 Hz
Control MethodScalar control
Protection FeaturesOvercurrent, overvoltage, undervoltage, short circuit
Communication InterfacesModbus RTU, Profibus DP, CANopen, Ethernet/IP
Enclosure RatingIP21
Ambient Temperature-10 to +50 °C
Input Voltage380 to 480 V AC
Cooling MethodAir cooling (natural convection or forced ventilation)

Related product manuals