11.11 o: KEYPAD
466 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o3-06
(0BDE)
AutoBackup Selection
Sets the function that automatically backs up parameters. This parameter is only
available when using an LCD keypad.
0 : Disabled
1 : Enabled
1
(0, 1)
815
o3-07
(0BDF)
AutoBackup Lapse
Sets the interval at which the automatic parameter backup function saves parameters
from the drive to the keypad.
Note:
This parameter is only available with an LED keypad.
1 : 10 minutes
2 : 30 minutes
3 : 60 minutes
4 : 12 hours
2
(1 - 4)
815
o4: MAINTENANCE MONITORS
No.
(Hex.)
Name Description
Default
(Range)
Ref.
o4-01
(050B)
Cum.Oper TimeSetting
Sets the initial value of the cumulative drive operation time in 10-hour units.
0 h
(0 - 9999 h)
815
o4-02
(050C)
Cum.Oper TimeSelect
Sets the condition that counts the cumulative operation time.
1 : Log Power-On Time
2 : Log Run Time
1
(1, 2)
815
o4-03
(050E)
Fan.Oper Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-
hour units.
0 h
(0 - 9999 h)
816
o4-05
(051D)
Cap.Maint.Setting
Sets the U4-05 [Capacitor Maintenance] monitor value.
0%
(0 - 150%)
816
o4-07
(0523)
PreChgRly Preset
Maintenance Cnt
Sets the U4-06 [SoftChgRelay Maint] monitor value.
0%
(0 - 150%)
816
o4-09
(0525)
IGBT Preset
Maintenance Cnt
Sets the U4-07 [IGBT Maintenance] monitor value.
0%
(0 - 150%)
816
o4-11
(0510)
Flt.History Initialization
Resets the records of Monitors [U2: FAULT] and [U3: FAULT HISTORY].
0 : No Reset
1 : Reset
0
(0, 1)
817
o4-12
(0512)
kWh Monitor
Initialization
Resets the monitor values for U4-10 [kWh Lower 4Digits] and U4-11 [kWh Upper
5Digits].
0 : No Reset
1 : Reset
0
(0, 1)
817
o4-13
(0528)
NumOfRunCom Init
Counter
Resets the monitor values for U4-02 [Num of Run Commands], U4-24 [No of Travels
(L)], and U4-25 [No of Travels(H)].
0 : No Reset
1 : Reset
0
(0, 1)
817
o4-22
(154F)
RUN
Time Format
Sets the time display format. This parameter is only available when using an LCD
keypad.
0 : 24 Hour Clock
1 : 12 Hour Clock
2 : 12 Hour JP Clock
0
(0 - 2)
817
o4-23
(1550)
RUN
Date Format
Sets the date display format. This parameter is only available when using an LED
keypad.
0 : YYYY/MM/DD
1 : DD/MM/YYYY
2 : MM/DD/YYYY
0
(0 - 2)
817
o4-24
(310F)
RUN
bAT Detection Selection
Sets operation when the drive detects bAT [Keypad Battery Low Voltage] and TiM
[Keypad Time Not Set].
0 : Disabled
1 : Enable (Alarm Detected)
2 : Enable (Fault Detected)
0
(0 - 2)
818

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals