11.15 U: MONITORS
480 SIEPYEUOQ2A01A AC Drive Q2A Technical Manual
No.
(Hex.)
Name Description MFAO Signal Level Ref.
U4-25
(07E7)
No of Travels(H) Shows the lower 4 digits of the drive run count.
Note:
The keypad shows the drive run count in 8 digits. Monitor U4-25 shows the upper 4
digits and U4-24 [No of Travels(L)] shows the lower 4 digits.
No signal output
available
-
U4-52
(1592)
Torque Ref from Comm Displays the torque reference given to the drive via a serial communication option card
or via Modbus communications as a decimal number.
Unit: 0.1%
No signal output
available
-
◆ U5: PID
No.
(Hex.)
Name Description MFAO Signal Level Ref.
U5-01
(0057)
PID Feedback Shows the PID control feedback value. Parameter b5-20 [PID Unit Selection] sets the
display units.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-02
(0063)
PID Input Shows the change between the PID setpoint and PID feedback (the quantity of PID
input) as a percentage of the maximum output frequency.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-03
(0064)
PID Output Shows the PID control output as a percentage of the maximum output frequency.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-04
(0065)
PID Setpoint Shows the PID setpoint. Parameter b5-20 [PID Unit Selection] sets the display units.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-05
(07D2)
PID Diff.Feedbk Shows the PID differential feedback value as a percentage of the maximum output
frequency.
This monitor is available after setting H3-02, H3-10, or H3-06 = 11 [MFAI Function
Select = Diff PIDFbk].
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-06
(07D3)
PID AdjustFeedback Shows the difference from calculating U5-05 - U5-01 [PID Diff.Feedbk] - [PID
Feedback].
Unit: 0.01%
Note:
U5-01 = U5-06 when H3-02, H3-10, or H3-06 ≠ 11 [MFAI Function Select = Diff
PIDFbk].
10 V: Maximum
frequency (-10 V to +10
V)
-
U5-21
(0872)
Expert
Energy Save Ki Coeff Shows the energy-saving coefficient Ki value for PM.
Unit: 0.01
No signal output
available
-
U5-22
(0873)
Expert
Energy Save Kt Coeff Shows the energy-saving coefficient Kt value for PM.
Unit: 0.01
No signal output
available
-
U5-99
(1599)
PID Setpoint Command Shows the PID setpoint command. Parameter b5-20 [PID Unit Selection] sets display
units.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
◆ U6: ADVANCED
No.
(Hex.)
Name Description MFAO Signal Level Ref.
U6-01
(0051)
Iq Sec Current Shows the value calculated for the motor secondary current as a percentage of the motor
rated secondary current. (q axis)
Unit: 0.1%
10 V: Motor secondary
rated current (-10 V to
+10 V)
-
U6-02
(0052)
Id ExcCurrent Shows the value calculated for the motor excitation current as a percentage of the motor
rated secondary current. (d axis)
Unit: 0.1%
10 V: Motor secondary
rated current (-10 V to
+10 V)
-
U6-03
(0054)
ASR Input Shows the ASR input value as a percentage of the maximum frequency.
Unit: 0.01%
10 V: Maximum
frequency (-10 V to +10
V)
-
U6-04
(0055)
ASR Output Shows the ASR output value as a percentage of the motor rated secondary current.
Unit: 0.01%
10 V: Motor secondary
rated current (-10 V to
+10 V)
-
U6-05
(0059)
Vq OutputVoltRef Shows the drive internal voltage reference for motor secondary current control. (q axis)
Unit: 0.1 V
400 V class: 10 V = 400
Vrms
(-10 V to +10 V)
-
U6-06
(005A)
Vd OutputVoltRef Shows the drive internal voltage reference for motor excitation current control. (d axis)
Unit: 0.1 V
400 V class: 10 V = 400
Vrms
(-10 V to +10 V)
-