Parameter List
11
11.8 H: TERMINALS
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 441
Setting Function Description Ref.
67 ModbusReg 1
The terminal activates when the bit specified by H2-08 [Mbus Reg1 Bit Select] for the Modbus register address set
with H2-07 [Mbus Reg1 Address Select] activates.
710
69 ModbusReg 2
The terminal activates when the bit specified by H2-10 [Mbus Reg2 Bit Select] for the Modbus register address set
with H2-09 [Mbus Reg2 Address Select] activates.
710
6A DataLog Error
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
711
90 to 93 Q2pack DO1 to 4
Sets the Q2pack digital output. Refer to the Q2pack online manual for more information.
711
A0 to A7 Q2pack ExDO1 to 8
Sets the digital output for the Q2pack DO-A3 option card. Refer to the Q2pack online manual for more
information.
711
100 to 1A7 Inverse Output of 0 to
A7
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which
function to inversely output.
711
H3: ANALOG INPUTS
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
AI1 Signal Level Select
Sets the input signal level for MFAI terminal AI1.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
713
H3-02
(0434)
AI1 Function Selection
Sets a function for MFAI terminal AI1.
4
(0 - 32)
713
H3-03
(0411)
RUN
AI1 Gain Setting
Sets the gain of the analog signal input to MFAI terminal AI1.
100.0%
(-999.9 - +999.9%)
713
H3-04
(0412)
RUN
AI1 Bias Setting
Sets the bias of the analog signal input to MFAI terminal AI1.
0.0%
(-999.9 - +999.9%)
714
H3-05
(0413)
AI3 Signal Level Select
Sets the input signal level for MFAI terminal AI3.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
0
(0 - 3)
714
H3-06
(0414)
AI3 Function Selection
Sets a function for MFAI terminal AI3.
1
(0 - 32)
714
H3-07
(0415)
RUN
AI3 Gain Setting
Sets the gain of the analog signal input to MFAI terminal AI3.
100.0%
(-999.9 - +999.9%)
714
H3-08
(0416)
RUN
AI3 Bias Setting
Sets the bias of the analog signal input to MFAI terminal AI3.
0.0%
(-999.9 - +999.9%)
715
H3-09
(0417)
AI2 Signal Level Select
Sets the input signal level for MFAI terminal AI2.
0 : 0 to 10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
2 : 4 to 20 mA
3 : 0 to 20 mA
2
(0 - 3)
715
H3-10
(0418)
AI2 Function Selection
Sets a function for MFAI terminal AI2.
4
(0 - 32)
715
H3-11
(0419)
RUN
AI2 Gain Setting
Sets the gain of the analog signal input to MFAI terminal AI2.
100.0%
(-999.9 - +999.9%)
715
H3-12
(041A)
RUN
AI2 Bias Setting
Sets the bias of the analog signal input to MFAI terminal AI2.
0.0%
(-999.9 - +999.9%)
716

Table of Contents

Other manuals for Omron Q2A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron Q2A Series and is the answer not in the manual?

Omron Q2A Series Specifications

General IconGeneral
BrandOmron
ModelQ2A Series
CategoryController
LanguageEnglish

Related product manuals