Parameter Details
12
12.1 A: INITIALIZATION
SIEPYEUOQ2A01A AC Drive Q2A Technical Manual 513
■ A1-11 Firmware Update Lock
No.
(Hex.)
Name Description
Default
(Range)
A1-11
(111D)
Expert
Firmware Update Lock
This function locks the drive firmware. When enabled, users cannot flash new drive firmware.
0
(0, 1)
0 : Disabled
Lock is disabled.
1 : Enabled
Lock is enabled.
■ A1-12 Bluetooth ID
No.
(Hex.)
Name Description
Default
(Range)
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a mobile device.
-
(0000 - 9999)
◆ A2: MANUAL SELECTION
You can register frequently used parameters and recently changed parameters here to access them quickly. You
can show the registered parameters in [Manual Parameters] in the main menu.
■ A2-01 to A2-32 MAN1 Param1 to MAN3 Param12
No.
(Hex.)
Name Description
Default
(Range)
A2-01 to A2-32
(0106 - 0125)
MAN1 Param1 to MAN3
Param12
You can select a maximum of 32 parameters or monitors for the drive and set them to parameters
A2-01 to A2-32. The [Manual Setup] section of the keypad shows the set parameters. You can
immediately access these set parameters.
Parameters in General-
Purpose Setup Mode
(Determined by A1-07)
Note:
• You must set A1-01 = 1 [Access Level = Manual Setup] to access parameters A2-01 to A2-32.
• When A1-07 = 1 or 2 [Q2pack Enable = Enable Q2pack or With DI], the drive saves q: Q2PACK PARAMETERS to A2-01 to A2-32.
The drive saves these parameters to A2-01 to A2-32.
• The drive saves a maximum of 32 parameters.
Note:
Set A1-01 = 2 [Standard Parameters] or A1-01 = 3 [Expert Parameters] to register the necessary parameters.
• The drive automatically saves changed parameters to A2-17 to A2-32.
Note:
Set Manual Autoset Parameters = 1 [Auto Save].
■ A2-33 Manual Autoset Parameters
No.
(Hex.)
Name Description
Default
(Range)
A2-33
(0126)
Manual Autoset Parameters
Sets the automatic save feature for changes to parameters MAN2 Param7 to MAN3 Param12.
0
(0, 1)
0 : Manual Entry
Set User Parameters manually.
1 : Auto Save
The drive automatically registers changed parameters to A2-17 to A2-32. The drive automatically saves the most
recently changed parameter to A2-17, and saves a maximum of 16 parameters. After the drive registers 16
parameters, when you save a new parameter, the drive will remove a parameter from the User Parameter list to
make space for the new parameter. The drive removes parameters with First In, First Out.
You can show the registered parameters in [Manual Parameters] in the main menu.