10-30 2000-OSM, F1
type: 10, channel: 0; input description: low hydrogen alarm
type: 11, channel: 0; input description: remote start/stop input
REMARKS Command
Description: Used for placing remarks in the BASIC program.
Syntax: REM remark
Example: 0010 REM CLEAR OUT COMMON!(1)
0020 COMMON!(1) = 0.0
REPORT TYPE Function
Description: Returns an integer indicating the report selected in the Printer Report Type
screen.
Syntax: REPORT_TYPE
Comments: 0 = RAW DATA and NEVER
1 = RAW DATA and ALWAYS
2 = RAW DATA and ON ALARM
4 = REGULAR and NEVER
5 = REGULAR and ALWAYS
6 = REGULAR and ON ALARM
8 = SHORT and NEVER
9 = SHORT and ALWAYS
10 = SHORT and ON ALARM
Example: 0010 IF REPORT_TYPE/4<>0 GOTO 9999
0020 LPRINT REPORT
0030 9999 END
If RAW DATA reports are selected on the Printer Report Type screen,
REPORT is printed; otherwise, nothing is printed.
REQUEST ANALYSIS Command
Description: Requests an analysis of a stream.
Syntax: RQANA(stream%)
Comments: stream% is the stream (from 1 to the maximum number of streams) to be
analyzed.
Example: 0010 RQANA(1)
Requests an analysis for stream one.
REQUEST BENCHMARK Command
Description Requests a benchmark of an analysis method.
Syntax: RQBEN(method%)
Comments method% is method (1-8) for which benchmark is to be performed.
Example: 0010 RQBEN(1)
Requests a benchmark analysis for method one.
REQUEST CALIBRATION Command
Description: Requests a calibration of an analysis method.
Syntax: RQCAL(method%)
Comments: method% is method (1-8) for which calibration is to be performed.
Example: 0010 RQCAL(1)
Requests a calibration analysis for method one.