EasyManuals Logo
Home>Allen-Bradley>Other>E300

Allen-Bradley E300 User Manual

Allen-Bradley E300
736 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #255 background imageLoading...
Page #255 background image
Rockwell Automation Publication 193-UM015E-EN-P - October 2015 255
Operating Modes Chapter 5
Figure 158 - Reversing Starter (Network & Local I/O) – Three-wire Control DeviceLogix Program,
Part C
Reversing Starter (Custom)
The E300 relay’s Operating Mode Reversing Starter (Custom) (Parameter 195 =
51) operates as a reversing starter with two output relays that are assigned as
normally open control relays. The Reversing Starter (Custom) operating mode is
used for applications that want customized DeviceLogix programs. This
operating mode requires minimal configuration rules.
Rules
1. Available for Control Module firmware v5.000 and higher.
2. Set two of the Output Ptxx Assignments (Parameters 202…204) to
Contr
ol Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
BrandAllen-Bradley
ModelE300
CategoryOther
LanguageEnglish

Related product manuals