508 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 8 Metering and Diagnostics
L1 Percent FLA
L1 Percent FLA (Parameter 47) reports the L1 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L1 Percent FLA = L1 Current / Full Load Amps
Table 460 - L1 Percent FLA (Parameter 47)
L2 Percent FLA
L2 Percent FLA (Parameter 48) reports the L2 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L2 Percent FLA = L2 Current / Full Load Amps
Table 461 - L2 Percent FLA (Parameter 48)
L3 Percent FLA
L3 Percent FLA (Parameter 49) reports the L3 current in comparison to the
active Full Load Amps programmed in FLA (Parameter 171) and FLA2
(Parameter 177).
L3 Percent FLA = L3 Current / Full Load Amps
Table 462 - L3 Percent FLA (Parameter 49)
Default Value 0.0
Minimum Value 0.0
Maximum Value 1000.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units %
Default Value 0.0
Minimum Value 0.0
Maximum Value 1000.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units %
Default Value 0.0
Minimum Value 0.0
Maximum Value 1000.00
Parameter Type UINT
Size (Bytes) 2
Scaling Factor 10
Units %