92 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
Input Pt03 Assignment (Parameter 199)
Input Pt03 Assignment (Parameter 199) allows you to assign this digital input
for the following functions:
Table 49 - Input Pt03 Assignment (Parameter 199)
Input Pt04 Assignment (Parameter 200)
Input Pt04 Assignment (Parameter 200) allows you to assign this digital input
for the following functions:
Table 50 - Input Pt04 Assignment (Parameter 200)
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 relay when it is in a tripped state
2 Remote Trip Force the E300 relay to go into a tripped state
3Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
4 Force Snapshot Force the E300 relay to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection
Value Assignment Description
0 Normal Function as a digital input
1 Trip Reset Reset the E300 relay when it is in a tripped state
2 Remote Trip Force the E300 relay to go into a tripped state
3Activate FLA2
Use the value in FLA2 Setting (Parameter 177) for the current-based protection
algorithms
4 Force Snapshot Force the E300 relay to update its Snapshot log
5 Emergency Start Issue an Emergency Start command
6 Test Mode Enable Test Mode monitoring
7 L1 Line Loss Arm Activate L1 Line Loss Protection
8 L2 Line Loss Arm Activate L2 Line Loss Protection
9 L3 Line Loss Arm Activate L3 Line Loss Protection
10 L1 L2 Line Loss Arm Activate L1 and L2 Line Loss Protection
11 L2 L3 Line Loss Arm Activate L2 and L3 Line Loss Protection
12 L1 L3 Line Loss Arm Activate L1 and L3 Line Loss Protection
13 L1 L2 L3 Line Loss Arm Activate L1, L2, and L3 Line Loss Protection