190 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 5 Operating Modes
Non-reversing Starter (Network & Operator Station) with Feedback
The E300 relay’s Operating Mode Non-Reversing Starter (Network& Operator
Station) with Feedback (Parameter 195 = 12) uses the network tag
LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and
the E300 Operator Station’s “I” and “0” keys in Local control mode to control
Relay 0, which controls the contactor coil. LogicDefinedPt00Data is a
maintained value, so the non-reversing starter remains energized when
LogicDefinedPt00Data has a value of 1 in Remote control mode. You can
program the appropriate state of the starter when communication is lost in
Remote control mode by using the Network Communication Fault and Network
Communication Idle parameters (Parameters 569 – 573) described in Chapter 4
.
The E300 Operator Station’s “I”, “0”, and “Local/Remote” keys are momentary
push buttons. Press and release the “I” button in Local control mode to energize
the starter. Press and release the “0” button in Local control mode to de-energize
the starter.
To change between Local and Remote control mode press and release the “Local/
Remote” button on the E300 Operator Station. The LED above “Local/Remote”
button illuminates yellow in Local control mode and red in Remote control
mode.
The auxiliary contact from the non-reversing starter’s contactor is wired into
Input 0. If a feedback signal is not received before the time identified in Feedback
Timeout (Parameter 213), then the E300 issues a trip or warning event.
The E300 issues a trip or warning event if the E300 Operator Station disconnects
from the base relay.
The reset button of the E300 Operator Station is enabled for this operating
mode.
Rules
1. Available for Control Module firmware v5.000 and higher.
2. Output Pt00 Assignment (Parameters 202) must be set to Control Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
4. Operator Station Trip must be disabled in TripEnableC (Parameter 186).
5. Operator Station Option Match Trip or Warning must be enabled.
• Option Match Trip or must be enabled in TripEnableC
(P
arameter 186)
The Non-reversing Starter (Network & Operator Station) operating mode uses
the value in network tag LogicDefinedPt00Data to control the starter. When
communication is restored between an automation controller and the E300,
the starter energizes if the value in LogicDefinedPt00Data is set to 1.