444 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 6 Protective Trip and Warning Functions
Analog Trip Status (Parameter 8) and Analog Warning Status (Parameter 14) are
used to monitor the respective analog-based protective trip and warning
functions.
Table 379 - Analog Trip Status (Parameter 8)
Table 380 - Analog Warning Status (Parameter 14)
Analog Module 1
The E300 Analog I/O Expansion Module scans up to three analog signals. An
over level trip or warning can be configured for each input channel.
Analog Module 1 – Channel 00 Over Level Trip
The E300 relay trips with an Analog Module 1 – Channel 00 Over Level Trip
indication if:
No trip currently exists
Analog Module 1 – Channel 00 Over Level Trip is enabled
Bit
1514131211109876543210 Function
XAnalog Module 1 - Input Channel 00 Trip
XAnalog Module 1 - Input Channel 01 Trip
XAnalog Module 1 - Input Channel 02 Trip
XAnalog Module 2 - Input Channel 00 Trip
XAnalog Module 2 - Input Channel 01 Trip
XAnalog Module 2 - Input Channel 02 Trip
XAnalog Module 3 - Input Channel 00 Trip
XAnalog Module 3 - Input Channel 01 Trip
XAnalog Module 3 - Input Channel 02 Trip
XAnalog Module 4 - Input Channel 00 Trip
XAnalog Module 4 - Input Channel 01 Trip
XAnalog Module 4 - Input Channel 02 Trip
Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Function
XAnalog Module 1 - Input Channel 00 Warning
XAnalog Module 1 - Input Channel 01 Warning
XAnalog Module 1 - Input Channel 02 Warning
XAnalog Module 2 - Input Channel 00 Warning
XAnalog Module 2 - Input Channel 01 Warning
XAnalog Module 2 - Input Channel 02 Warning
X Analog Module 3 - Input Channel 00 Warning
X Analog Module 3 - Input Channel 01 Warning
XAnalog Module 3 - Input Channel 02 Warning
XAnalog Module 4 - Input Channel 00 Warning
XAnalog Module 4 - Input Channel 01 Warning
XAnalog Module 4 - Input Channel 02 Warning

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
BrandAllen-Bradley
ModelE300
CategoryOther
LanguageEnglish

Related product manuals