84 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
Operator Station Type (Parameter 224)
The E300 relay offers two different types of operator stations. Place the value of
the expected operator station into Parameter 224. A value of (0) disables the
Option Match feature for the operator station. A value of (1), “No Operator
Station”, makes the operator station not allowed on the Expansion Bus and
prevents you from connecting an operator station to the E300 relay system.
Table 35 - Operator Station Type (Parameter 224)
Digital I/O Expansion Module 1 Type (Parameter 225)
The E300 relay supports up to four additional Digital I/O expansion modules.
This parameter configures the Option Match feature for the Digital I/O
expansion module set to Digital Module 1. There are three different types of
Digital I/O expansion modules. Place the value of the expected Digital I/O
expansion module set to Digital Module 1 into Parameter 225. A value of (0)
disables the Option Match feature for this Digital I/O expansion module. A
value of (1), “No Digital I/O Expansion Module”, makes the Digital I/O
expansion module set to Digital Module 1 not allowed on the Expansion Bus and
prevents you from connecting a Digital I/O expansion module set to Digital
Module 1 to the E300 relay system.
Table 36 - Digital I/O Expansion Module 1 Type (Parameter 225)
Code Description Operator Station Cat. No.
0Ignore —
1 No Operator Station (Operator Station Not Allowed) —
2 Control Station 193-EOS-SCS
3 Diagnostic Station with LCD 193-EOS-SDS
Code Description Digital I/O Expansion Module Cat. No.
0 Ignore —
1
No Digital I/O Expansion Module (Digital I/O Expansion
Module Not Allowed)
—
2 4 Inputs, 24V DC / 2 Relay Outputs 193-EXP-DIO-42-24D
3 4 Inputs, 110-120V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-120
4 4 Inputs, 220-240V AC 50/60Hz / 2 Relay Outputs 193-EXP-DIO-42-240