80 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 4 System Operation and Configuration
Table 28 - Invalid Configuration Cause (Parameter 39)
The Trip/Warn LED on the Communication Module and Operator Stations
flashes a pattern of red, 3 long and 8 short blinks, and bits 0 and 2 in Device
Status 0 (Parameter 20) are set to 1 when the device is in Invalid Configuration
Mode.
Table 29 - Invalid Configuration Mode Bit Function Detail — Device Status 0 (Parameter 20)
To return to Ready/Run Mode, place a valid configuration value in the parameter
that is identified by Invalid Configuration Parameter (Parameter 38) and Invalid
Configuration Cause (Parameter 39). Reset the trip state of the E300 relay by
pressing the blue reset button on the Communication Module, via network
communication, with the internal web server of the EtherNet/IP communication
module, or by an assigned digital input.
Option Match
Due to the modular nature of the E300 relay, you can enable the Option Match
feature to ensure that the options that were expected for the motor protection
application are the ones that are present on the E300 relay system. You can
configure an option mismatch to cause a protection trip or provide a warning
within the E300 relay.
Code Description
0No Error
1 Value over maximum value
2 Value under minimum value
3 Illegal value
4 L3 Current detected (for single-phase applications)
5 CopyCat error
Bit
1514131211109876543210 Function
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved