Rockwell Automation Publication 193-UM015E-EN-P - October 2015 467
Protective Trip and Warning Functions Chapter 6
Table 407 - Analog Module 3 – Channel 02 Warning Level (Parameter 525)
Analog Module 4
The E300 Analog I/O Expansion Module scans up to three analog signals. An
over level trip or warning can be configured for each input channel.
Analog Module 4 – Channel 00 Over Level Trip
The E300 relay trips with an Analog Module 4 – Channel 00 Over Level Trip
indication if:
No trip currently exists
Analog Module 4 – Channel 00 Over Level Trip is enabled
The measured analog input signal is greater than the Analog Module 4
C
ha
nnel 00 Trip Level for a time period greater than the Analog Module 4
– Channel 00 Over Level Trip Delay.
If the E300 relay trips on an Analog Module 4 – Channel 00 Over Level, the:
TRIP/WARN LED status indicator flashes a red 4-long / 10-short blink
patter
n
Bit 9 in Analog Trip Status (Parameter 8) sets to 1
Bit 0 in Device Status 0 (Parameter 20) sets to 1
Any relay outputs configured as a Trip Relay open
Any relay outputs configured as a Control Relay open
Any relay outputs configured as a Trip Alarm close
Any relay outputs configured as a Normal Relay are placed in their
P
r
ote
ction Fault state (if so programmed)
Default Value 0
Minimum Value -32768
Maximum Value 32767
Parameter Type INT
Size (Bytes) 2
Scaling Factor 1
Units

Table of Contents

Other manuals for Allen-Bradley E300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley E300 and is the answer not in the manual?

Allen-Bradley E300 Specifications

General IconGeneral
BrandAllen-Bradley
ModelE300
CategoryOther
LanguageEnglish

Related product manuals