Protective Trip and Warning Functions Chapter 6
Table 407 - Analog Module 3 – Channel 02 Warning Level (Parameter 525)
Analog Module 4
The E300 Analog I/O Expansion Module scans up to three analog signals. An
over level trip or warning can be configured for each input channel.
Analog Module 4 – Channel 00 Over Level Trip
The E300 relay trips with an Analog Module 4 – Channel 00 Over Level Trip
indication if:
• No trip currently exists
• Analog Module 4 – Channel 00 Over Level Trip is enabled
• The measured analog input signal is greater than the Analog Module 4 –
C
ha
nnel 00 Trip Level for a time period greater than the Analog Module 4
– Channel 00 Over Level Trip Delay.
If the E300 relay trips on an Analog Module 4 – Channel 00 Over Level, the:
• TRIP/WARN LED status indicator flashes a red 4-long / 10-short blink
patter
n
• Bit 9 in Analog Trip Status (Parameter 8) sets to 1
• Bit 0 in Device Status 0 (Parameter 20) sets to 1
• Any relay outputs configured as a Trip Relay open
• Any relay outputs configured as a Control Relay open
• Any relay outputs configured as a Trip Alarm close
• Any relay outputs configured as a Normal Relay are placed in their
P
r
ote
ction Fault state (if so programmed)
Default Value 0
Minimum Value -32768
Maximum Value 32767
Parameter Type INT
Size (Bytes) 2
Scaling Factor 1
Units