496 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 8 Metering and Diagnostics
Operator Station Status
Operator Station Status (Parameter 19) reports the state of the E300 relay
Operator Station input buttons and output LEDs.
Table 434 - Operator Station Status (Parameter 19)
Bit
1514131211109876543210 Function
X Operation Station I
X Operation Station II
X Operation Station Local Remote
X Operation Station O
X Operation Station Reset
Reserved
Reserved
Reserved
X Operation Station I LED
X Operation Station II LED
X Operation Station Local LED
X Operation Station Remote LED
X Operation Station O LED
Reserved
Reserved
Reserved