Rockwell Automation Publication 193-UM015E-EN-P - October 2015 79
System Operation and Configuration Chapter 4
Table 27 - Run Mode Bit Function Detail — Device Status 0 (Parameter 20)
Test Mode
Test Mode is used by installers of motor control centers who are testing and
commissioning motor starters with an automation system. A digital input of the
E300 relay is assigned to monitor the Test position of the motor control center
enclosure. The Input Assignments (Parameters 196…201) are described later in
this chapter.
Anyone who commissions motor starters in an automation system can put their
motor control center enclosure into the Test position to activate Test Mode and
verify that the digital inputs and relay outputs of the E300 relay are operating
properly with the motor starter without energizing power to the motor. If the
E300 relay senses current or voltage in Test Mode, it generates a Test Mode Trip.
Invalid Configuration Mode
Invalid Configuration Mode is an active mode for the E300 relay in which the
relay is in a tripped state due to invalid configuration data. Invalid Configuration
Parameter (Parameter 38) indicates the parameter number that is causing the
fault. Invalid Configuration Cause (Parameter 39) identifies the reason for
Invalid Configuration Mode.
Bit
1514131211109876543210 Function
X Trip Present
X Warning Present
X Invalid Configuration
X Current Present
X GFCurrent Present
X Voltage Present
X Emergency Start Enabled
X DeviceLogix Enabled
X Feedback Timeout Enabled
X Operator Station Present
X Voltage Sensing Present
X Intern Ground Fault Sensing Present
X Extern Ground Fault Sensing Present
XPTC Sensing
XReady
Reserved