EasyManuals Logo
Home>Allen-Bradley>Other>E300

Allen-Bradley E300 User Manual

Allen-Bradley E300
736 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #570 background imageLoading...
Page #570 background image
570 Rockwell Automation Publication 193-UM015E-EN-P - October 2015
Chapter 10 EtherNet/IP Communication
Table 564 - Device Conflict over Duplicate IP Addresses
DNS Addressing
To further qualify a module’s address, use DNS addressing to specify a host name
for a module, which also includes specifying a domain name and DNS servers.
DNS addressing makes it possible to configure similar network structures and IP
address sequences under different domains.
DNS addressing is only necessary if you see the module by host name, such as in
path descriptions in MSG instructions.
To use DNS addressing, perform this procedure.
1. Assign a host name to the module.
2. Configure the module's parameters.
In addition to the IP address, subnet mask, and gateway address, you must
configu
re a host name for the module, domain name, and primary/secondary
DNS server addresses.
Electronic Data Sheet (EDS)
File Installation
Before the E300 relay EtherNet/IP Communication Module is configured to
communicate on an EtherNet/IP network, it must be registered to the software
that configures the network (for example, RockwellAutomation RSLinx Classic
and RSNetWorx for EtherNet/IP software). Register the module by installing an
EDS file. The EDS file for the E300 relay EtherNet/IP Communication Module
can be obtained from one of two locations:
Emb
edded in the module
The Allen-Bradley EDS file download website.
If then
both modules support duplicate IP
address detection,
the first started module uses and retains its IP address.
The other module detect sa conflict, gives up the IP
address, and enters conflict mode.
both modules support duplicate IP
address detection and are started at
roughly the same time,
one of the modules surrenders the IP address and enters
conflict mode.
one module supports duplicate IP address
detection and a second module does not,
the second module generally keeps its IP address,
regardless of which module first obtains the IP address.
The module that supports duplicate IP address detection
detects the conflict and gives up the IP address.
NOTE: Contact the network administrator to have a host name assigned. Valid host
names should be compliant with IEC-1131-3.

Table of Contents

Other manuals for Allen-Bradley E300