Operating Modes Chapter 5
Figure 98 - Non-reversing Starter (Network & Operator Station) with Feedback DeviceLogix
Program, Part B
Non-reversing Starter (Network & Local I/O) – Two-wire Control
The E300 relay’s Operating Mode Non-Reversing Starter (Network & Local I/O)
– Two Wire Control (Parameter 195 = 16) uses the network tag
LogicDefinedPt00Data in Output Assembly 144 in Remote control mode and
Input 0 in Local control mode to control Relay 0, which controls the contactor
coil. Input 1 determines if the motor starter is in Remote or Local control mode.
LogicDefinedPt00Data is a maintained value, so the non-reversing starter
remains energized when LogicDefinedPt00Data has a value of 1 in Remote
control mode. You can program the appropriate state of the starter when
communication is lost in Remote control mode by using the Network
Communication Fault and Network Communication Idle parameters
(Parameters 569 – 573) described in Chapter 4
In Local control mode, the state of Input 0 controls Output Relay 0, which
controls the contactor coil. Input 0 is a maintained value, so the non-reversing
starter remains energized when Input 0 is active.