the trip number into the parameter. The trip can be made to stop the drive and then trip, by enabling the associated bit parameter.
Trips that cannot be masked are UV, AOC, AtL.Err, PS, O.SPd, FOC, O.ht1, O.ht2, O.ht3, EEF, SLX.HF, S.OV, PLL Err, Enc9, SLAVE.Er and HF17 to
HF29.
Example 1.
The user wants the drive to not trip when there is current loss on analog input 2. Enter 28 into Pr
10.52
and set Pr
10.62
to 0.
Example 2.
The user wants the drive to stop and then trip when there is current loss on analog input 2. Enter 28 into Pr
10.52
to achieve this.
"__
"No bridge
"_1
"Bridge 1 active
"2_
"Bridge 2 active
Where _ is a blank.
When the armature voltage exceeds 1.15 times the supply voltage the armature voltage clamp is activated to prevent the voltage rising. SCR firing is
inhibited until the voltage has fallen.
Mentor MP Advanced User Guide
143
Issue Number: 4
www.onxcontrol.com
10.72