Exception
message
format
format
Advanced parameter
descriptions
Serial
comms
The slave processes the write block in the order the data is received. If a
write fails due to an out of range value then the write block is terminated.
However, the slave does not raise an exception response, rather the
error condition is signalled to the master by the number of successful
writes field in the response.
Parameter
over
range
during
block
read/write
FC23
There will be no indication that there has been a value out of range
during a FC23 access.
6.2.9
CRC
The CRC is a 16bit cyclic redundancy check using the standard CRC-16
polynomial x16 + x15 + x2 + 1. The 16bit CRC is appended to the
message and transmitted LSB first.
The CRC is calculated on ALL the bytes in the frame.
6.2.10
Device
compatibility
parameters
210
Mentor MP Advanced User Guide
www.onxcontrol.com
Issue Number: 4
Parameter
must wait for this time before issuing a
new message. In a network of devices,
the slowest time must be used
Maximum