A sliding window filter may be applied to the feedback taken from the drive encoder. This is particularly useful in applications where the drive encoder
is used to give speed feedback for the speed controller and where the load includes a high inertia, and so the speed controller gains are very high.
Under these conditions, without a filter on the feedback, it is possible for the speed loop output to change constantly from one current limit to the other
and lock the integral term of the speed controller.
the number of encoder lines per revolution (Pr
3.34
{
Fb05,
0.75
}) has been set up correctly. This may then be scaled and routed to any non-protected
drive parameter.
the encoder input as a percentage of the maximum drive encoder reference provided that the number of encoder lines per revolution (Pr
3.34
{
Fb05,
0.75
}) has been set up correctly. This may then be scaled and routed to any non-protected drive parameter.
complete. To allow detection of non initialized state Pr
3.48
remains zero for 500µs.