7-4
Tag Data Links with Other Models
The performance of tag data links depends on the CPU Unit model and EtherNet/IP Unit model as
shown below.
When you use tag data links between the built-in EtherNet/IP port on an NJ/NX-series CPU Unit and
another CPU Unit or EtherNet/IP Unit, configure the tag data link settings based on either Unit, which-
ever has the lower level of communications performance.
Differences in Tag Data Link Performance Specifications
Item
NX-series CPU Unit
NJ-series CPU Unit
CJ2M-CPU3£
CS1W-EIP21
CJ1W
-EIP21
CJ2H-CPU6£-
EIP
NX701 NX102 NX1P2
Unit version
Unit ver-
sion 1.00
to 1.02
Unit ver-
sion 1.03
or later
2.0
2.1 or lat-
er
Tag Total size
of all tags
184,832
words
(total of
369,664
words with
the two
ports)
9,600
words (to-
tal of
19,200
words with
the two
ports)
9,600 words 640 words 184,832 words
Maximum
size of tag
722 words
(721
words
when the
tag set in-
cludes the
Controller
status)
300 words
(299 words when the tag set includes the Control-
ler status)
20 words
(19 words
when the
tag set in-
cludes the
Controller
status)
640 words
(639
words
when the
tag set in-
cludes the
Controller
status)
722 words
(721 words when
the tag set in-
cludes the Con-
troller status)
Number of
registrable
tags
256
(total of 512 with the
two ports)
256
*1
32 256
Tag set Maximum
size of tag
set
722 words
(721
words
when the
tag set in-
cludes the
Controller
status)
300 words
(299 words when the tag set includes the Control-
ler status)
20 words
(19 words
when the
tag set in-
cludes the
Controller
status)
640 words
(639
words
when the
tag set in-
cludes the
Controller
status)
722 words
(721 words when
the tag set in-
cludes the Con-
troller status)
Number of
tags per
tag set
8
(7 tags when the tag set includes the Controller status)
Note: Input and output variables cannot be combined in one tag set.
Number of
registrable
tag sets
256
(total of
512 with
the two
ports)
32 (total of
40 with the
two
ports)
*2
32 32 256
7 Tag Data Link Functions
7-86
NJ/NX-series CPU Unit Built-in EtherNet/IP Port Users Manual (W506)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX102-12 Series and is the answer not in the manual?

Omron NX102-12 Series Specifications

General IconGeneral
BrandOmron
ModelNX102-12 Series
CategoryController
LanguageEnglish

Related product manuals