429
Temperature Sensor Units Section 7-5
7-5 Temperature Sensor Units
CP1W-TS002/TS102 and CPM1A-TS002/TS102 Temperature Sensor Units
each provide up to four input points, and CP1W-TS001/TS101 and CPM1A-
TS001/TS101 Temperature Sensor Units each provide up to two input points.
The inputs can be from thermocouples or platinum resistance thermometers.
CP1W-TS002/TS102 and CPM1A-TS002/TS102 Temperature Sensor Units
are each allocated four input words, so no more than three Units can be con-
nected. Up to 14 temperature sensor input points can be connected by using
three CP1W-TS002/TS102 or CPM1A-TS002/TS102 Temperature Sensor
Units and one CP1W-TS001/TS101 or CPM1A-TS001/TS101 Temperature
Sensor Unit.
MOV(021)
#8051
102
First Cycle ON Flag
A200.11
TIM5
#0002
Always ON Flag
P_On
002
D0
T5
MOV(021)
(P_EQ)
110.00
003
D1
T5
MOV(021)
D10
102
T5
MOV(021)
003
#8000
T5
CMP(020)
Execution
condition
Execution
condition
Execution
condition
Execution
condition
← Writes the range code (8051) to the Unit.
← Reads analog input 0's converted value.
← Reads analog input 1's converted value.
← The content of D10 is written to the output
word as the analog output set value.
Open-circuit alarm