430
Temperature Sensor Units Section 7-5
Part Names
Temperature Sensor Units:
CP1W-TS and CPM1A-TS
(1) Temperature Sensor Input Terminals
Used to connect temperature sensors such as thermocouples or plati-
num resistance thermometers.
(2) DIP Switch
Used to set the temperature unit (°C or °F) and the number of decimal
places used.
(3) Rotary Switch
Used to set the temperature input range. Make the setting according to
the specifications of the temperature sensors that are connected.
(4) Expansion I/O Connecting Cable
Connected to the expansion connector of a CP1H CPU Unit or a CP-
series Expansion Unit or Expansion I/O Unit.The cable is included with
the Temperature Sensor Unit and cannot be removed.
Note Do not touch the cables during operation. Static electricity may
cause operating errors.
(5) Expansion Connector
Used for connecting CP-series Expansion Units or Expansion I/O Units.
Main Specifications
Note Accuracy for a K-type sensor at −100°C or less is ±4°C ±1 digit max.
(5) Expansion Connector
(1) Temperature Sensor Input Terminals
(4) Expansion I/O
Connector Cable
(3) Rotary Switch
(2) DIP Switch
Item CP1W-TS001
CPM1A-TS001
CP1W-TS002
CPM1A-TS002
CP1W-TS101
CPM1A-TS101
CP1W-TS102
CPM1A-TS102
Temperature sensors Thermocouples Platinum resistance thermometer
Switchable between K and J, but same type
must be used for all inputs.
Switchable between Pt100 and JPt100, but
same type must be used for all inputs.
Number of inputs2424
Allocated input words2424
Max. number of Units3131
Accuracy (The larger of ±0.5% of converted value or
±2°C) ±1 digit max. (See note.)
(The larger of ±0.5% of converted value or
±1°C) ±1 digit max.
Conversion time 250 ms for 2 or 4 input points
Converted temperature data 16-bit binary data (4-digit hexadecimal)
Isolation Photocouplers between all temperature input signals
Current consumption 5 VDC: 40 mA max., 24 VDC: 59 mA max. 5 VDC: 54 mA max., 24 VDC: 73 mA max.