1-101
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
1.8.4 Setting Alarms
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Math channel settings >
Alarm
Web application: Config. tab > Math channel settings > Channel range (display example:
A001-A020) > Alarm
Hardware configurator: Setting tab > Math channel settings > Channel range (display
example: A001-A020) > Alarm
Description
Setup Item Selectable Range or Options Default Value
First-CH GX20/GP20: A001 to A100
GX10/GP10: A001 to A050
A001
Last-CH Same as the first channel A001
First-CH, Last-CH
Set the target channels.
Level 1, Level 2, Level 3, Level 4
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
Type
1
H: High limit, L: Low limit, T: Delay high limit,
t: Delay low limit
H: High limit
Value
1
-9999999 to 99999999 0.00
Hysteresis
1, 3
Numeric value (0 to 100000) 0.00
Logging
1
Off, On On
Output type
1
Off, Relay, Internal switch Off
Output No.
2
DO channel or internal switch —
1 Appears when On/Off is set to On.
2 Appears when Output type is not set to Off.
3 Appears when the type is set to H:High limit or L:Lowlimit.
On/Off
To use an alarm level (1 to 4), set this to On.
Type
Set the alarm type.
For details, see page 1-35 in section 1.2.2, “Setting Alarms”.
Value
Set the alarm value for the specified alarm type.
Options Value
H, L Within –9999999 to 99999999 excluding the decimal point.
T, t Same as H and L
1.8ConfiguringMathChannels(/MToption)