1-170
IM 04L51B01-01EN
1.19.2 EventActionExamples
Example1:Starting/StoppingRecordingthroughRemoteControl
Starts or stops recording when a remote control signal is applied to DI channel 0101. This
example assumes that a DI module is installed in slot 1 of the GX/GP. We assume that a
DI module is installed in slot 1 of the GX/GP main unit and that the operation mode is set to
Remote. Use event action number 1.
Setting the Mode of the DI Module
• SetupScreen
MENU key > Browse tab > Setting > Setting menu Measurement settings > Module
settings Select module > Module 1 GX90XD-16-11N
• SetupItems
Setup Item Value
Operation mode Operation mode Remote
ConfiguringtheEventAction
• SetupScreen
MENU key > Browse tab > Setting > Setting menu Display settings > Eventaction
• SetupItems
Setup Item Value
Event action number 1
Event action On/Off On
Event Type Remote
Number 0101
Operation mode Rising / Falling edge
Action Type Recording start/stop
Operation
If the DI channel 0101 input is turned on when recording is stopped, recording starts. If the
DI channel 0101 input is turned off when recording is in progress, recording stops.
Example2:WritingaMessageWhenanAlarmOccurs
Write the message “Channel 1 Alarm” to group 1 when an alarm occurs on channel 0001.
This example assumes that an AI module is installed in slot 0 of the GX/GP. Use event
action number 2.
ConfiguringtheEventAction
• SetupScreen
MENU key > Browse tab > Setting > Setting menu Display settings > Eventaction
• SetupItems
Setup Item Value
Event action number 2
Event action On/Off On
Event Type Alarm - IO channel
Number 0001
Alarm level 1
Operation mode Rising edge
Action Type Message
Number 1
Detail Specified
Group number 1
Other Settings
Set AI channel 0001 to alarm level 1.
Setup: See page 1-35 in section 1.2.2, “Setting Alarms”.
Register “Channel 1 Alarm” in message number 1.
Setup: See page 1-113 in section 1.10.3, “Setting Messages”.
1.19ConfiguringtheEventActionFunction

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA GX20 and is the answer not in the manual?

YOKOGAWA GX20 Specifications

General IconGeneral
BrandYOKOGAWA
ModelGX20
CategoryRecording Equipment
LanguageEnglish

Related product manuals