1-257
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
Note
• Do not carry out the following operations while the GX/GP is reconfiguring. Doing so may cause
damage.
Turn the power off and on.
Insert or remove modules.
• If turn off a expansion module and turn it back on, after checking the connected module,
execute reconfiguration.
• If the total number of I/O channels of the installed modules exceeds 100 on the GX10/GP10/
GX20-1/GP20-1 or 500 on the GX20-2/GP20-2, no additional modules can be reconfigured.
For example, if the maximum number of I/O channels are assigned and the last channel is
assigned to an intermediate channel of an installed I/O module, that module and subsequent
modules will not be reconfigured or identified.
Module
n
• • •
1
10
Module
1
:
81
90
:
91
100
106
:
:
Maximum number
of I/O channels
This module will not be detected.
Example GX10/GX20-1
• If the measurement mode is high speed, dual interval or if the advanced security function is
enabled, PID control modules will not be identified.
• During reconfiguration, the output channel is turned off or de-energized. In addition, for models
with the program control function (/PG), the program pattern is changed when the PID control
module is removed.
ConditionsontheCombinationofFirmwareVersionsandModules
The module versions that can be detected depending on the firmware version are as follows.
If an installed module cannot be detected, update the firmware.
Module FirmwareVersion
Name Model Type
Analog Input GX90XA -U2 (Universal) R1.01.X or later
-T1 (Electromagnetic relay) R1.03.X or later
-C1 (Current (mA)) R2.01.X or later
-L1 (Low withstand voltage) R2.01.X or later
-H0 (high-speed universal) R4.01.X or later
-R1 (4-wire RTD/resistance) R4.01.X or later
Digital Input GX90XD R1.01.X or later
Digital Input/Output GX90WD R2.01.X or later
Digital Output GX90YD R1.01.X or later
Pulse Input GX90XP R3.01.X or later
Analog output GX90YA R3.02X or later
PID control GX90UT R4.01.X or later
Expansion Module GX90EX R2.01.X or later
1.29.5 Adjusting the Touch Screen
See page 5-18 in section 5.1.6, “Adjusting and Checking the Touch Screen”.
1.29InitializingandCalibratingtheSystem(Initialization,reconfiguration,touchscreencalibration),SettingtheMeasurementMode