1-133
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
1.12.2 Configuring Recording Channels
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Recording settings >
Recording channel settings
Web application: Config. tab > Recording settings > Recording channel settings
Hardware configurator: Recording settings > Recording channel settings
Description
Setup Item Selectable Range or Options Default Value
Display data, Trend waveform AI, DI, pulse input, DO, AO, PID, math,
communication channels
—
Event data AI, DI, pulse input, DO, AO, PID, math,
communication channels
—
Manual sample AI, DI, pulse input, DO, AO, PID, math,
communication channels
—
Displaydata,Trendwaveform
Set the channels for recording display data. Channels that you can specify are displayed.
Even when recording mode is set to Event, if trend rate switching is set to On, set separate
channels from the recording channels of event data.
Eventdata
Set the channels for recording event data. Channels that you can specify are displayed.
If you specify more than the number of recordable channels, the recording interval will
automatically change to a setting that is possible.
Manual sample
Set the channels for recording manual sampled data. Channels that you can specify are
displayed.
Number of Recording Channels
Model Maximum Number of Channels
GX10/GP10 50
GX20-1/GP20-1 50
GX20-2/GP20-2 100
Manual sampled data is recorded to internal memory. If the number of manual sampled data
entries exceeds 400, the data is overwritten from the oldest entry.
Time
Manual sampled data
1.12SettingRecordingConditions(Recordingmode,recordinginterval,savinginterval)