1-162
IM 04L51B01-01EN
1.19 ConfiguringtheEventActionFunction
The event action function is used to execute a specified action on the basis of events that
occur. The settings explained here are also used to configure the remote control function.
1.19.1 SettingEventActionNumbersandActions
Select an event action number, and set event action to On.
Set the even type and event-specific conditions.
Then, set the action for the event and the action conditions.
Path
GX/GP: MENU key > Browse tab > Setting > Setting menu Eventaction
Web application: Config. tab > Eventaction > Eventactionnumber(displayexample:
1-20)
Hardware configurator: Eventaction > Eventactionnumber(displayexample:1-20)
Description
Setup Item Selectable Range or Options Default Value
Event action number 1 to 50 1
Eventactionnumber
Select the event action number to assign an event action.
Eventaction
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
On/Off
Select On to use the event action function.
Event
1
Setup Item Selectable Range or Options Default Value
Type Internal switch, Remote,
4
Relay, Alarm - IO channel,
Alarm - Math channel, Alarm - Communication
channel, Any alarm, Timer, Match time timer, User
function key
8
, Status
8
Internal switch
Number
2
IO channel, Math channel, Communication channel,
Internal switch, Timer, Match time timer, User function
key, Relay, Remote
1
Alarm level
3
1 to 4 1
Event details
6
Recording, Math, User lock out
7
, Under login
7
, Memory/
Media error, Measurement error, Communication error
Recording
Operation mode Rising edge, Falling edge, Rising/Falling edge, Edge
5
Rising edge
1 Appears when Event action is set to On.
2 Does not appear when Type is set to Any alarm.
3 Appears when the Type is to Alarm - I/O channel, Alarm - Math channel, or Alarm -
Communication channel.
4 Appears when the operation mode of the DI module is set to Remote.
5 Appears when the event is set to Timer or Match time timer.
6 Appears when the type is set to Status.
7 Appears for the advanced security function (/AS option).
8 Release number 2 and later.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA GX20 and is the answer not in the manual?

YOKOGAWA GX20 Specifications

General IconGeneral
BrandYOKOGAWA
ModelGX20
CategoryRecording Equipment
LanguageEnglish

Related product manuals