EasyManuals Logo
Home>YOKOGAWA>Recording Equipment>GX20

YOKOGAWA GX20 User Manual

YOKOGAWA GX20
707 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #545 background imageLoading...
Page #545 background image
5-11
IM 04L51B01-01EN
Maintenance and Troubleshooting
1
2
3
4
5
App
Index
Note
Do not perform any other operations (especially turning the GX/GP off) during calibration.
The GX/GP may malfunction.
5.1.4 Calibrating the D/A of AO Modules and Adjusting the Output Accuracy
Required Instruments
To adjust AO modules, you need calibration instruments with the following specifications and
accuracy.
• Resistance standard : Resisitance value: 600 Ω or less
Accuracy: ±0.01% or more
Allowable power: 0.25 W or higher
Temperature coefficient: 5ppm/°C or less
• Digital Multimeter : Accuracy: ±0.01% or more
For information on purchasing these calibration instruments, contact the YOKOGAWA dealer that you
purchased the GX/GP from.
Preparing the Instruments
1
Wire the channel of the AO module to be calibrated and the calibration instruments as
shown in the following figure, and adequately warm up the instruments (the warm-up
time of the GX/GP is at least 30 minutes).
2
Check that the operating environment such as ambient temperature and humidity is
within the standard operating conditions. (See the general specifications.)
Operation complete
–
CH1 output terminal
+
Digital multimeter
.
Resistor
–
+
CH1 output terminal
Digital multimeter
Current input terminal
.
Wiring for current measurement
Wiring for voltage measurement
5.1 Maintenance

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA GX20 and is the answer not in the manual?

YOKOGAWA GX20 Specifications

General IconGeneral
BrandYOKOGAWA
ModelGX20
CategoryRecording Equipment
LanguageEnglish

Related product manuals