Program Operation Status
Data Register Description Data Type
Program operation status 308101 1: Program operation stop,
operation end
2: Program running
16-bit signed integer
Running pattern number
display
308102 1 to 99
Running segment number
display
308103 1 to 99
0: Program stopped
Wait state 308104 0: Not waiting
1: Waiting
Remaining segment time of
the running pattern (hours:
0 to 99)
308105 0 to 99 (hours)
Remaining segment time
of the running pattern
(minutes: 0 to 59)
308106 0 to 59 (minutes)
Remaining segment time
of the running pattern
(seconds: 0 to 59)
308107 0 to 59 (s)
PV event status 308111
|
308142
0: Event absent
1: Event present
Time event status 308151
|
308182
0: Event absent
1: Event present