1-31
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
Low-cut
1
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
Low-cut value
2
0.0% to 5.0% 0.0
Low-cut output
3
Output 0%, Output linear Output 0%
1 Appears when the type is set to Volt and Calculation is set to Square root or when the type is
set to GS and Calculation is set to Linear scaling or Square root.
2 Appears when On/Off is set to On.
3 Does not appear when the type is set to GS and Calculation is set to Linear scaling.
On/Off
Select On to use the low-cut function.
Low-cutvalue
Set the low-cut value in the range of 0.0% to 5.0% of the input span.
Input value
Measured value
Result of square root computation
Low-cut value
Low-cutoutput
Set the output value when the input is less than the low-cut value for when the low-cut
function is in use.
Options Description
Output 0% Set the value for 0%.
Output linear Outputs values that result by applying linear scaling to the input on the basis of
the specified span and scale.
Note
When the type is set to GS and Calculation is set to Linear scaling, the low-cut output is fixed to
Output 0%.
Moving average
Setup Item Selectable Range or Options Default Value
On/Off Off, On Off
Count
1
2 to 100
2 to 500 (high-speed AI)
2
1 Appears when On/Off is set to On.
On/Off
Set this to On to perform moving average.
Count
Set the number of data points to take the moving average of.
Average
Scan interval
Average
1.2ConfiguringAIChannels(Analog(includingDI)input)channelsandAI(mA)channels