General
Specications
GS 04L53B01-31EN
GX90UT PID Control Module
GX10/GX20/GP10/GP20 Paperless Recorder
Data Acquisition System GM
Loop Control Function, Program Control Function (/PG Option)
GS 04L53B01-31EN
2017.06.26 2nd Edition (YK)
Overview
The GX90UT is a PID control module that connects to
the GX/GP, expandable I/O units, and GM main units
and sub units.
● TheGX90UTPIDControlModulecanperform
PIDcontrolonuptotwoloops.Itisequippedwith
twocontrolinputs,twocontroloutputs,eightdigital
inputs,andeightdigitaloutputs.Inadditiontosingle
loopcontrol,cascadecontrolandloopcontrolwith
PVswitchingarepossible.Forthecontroloutput,
youcanselectcurrentoutputorvoltagepulsefor
eachloop.
● InstallingthePIDControlModuleintheGX/GP/GM
enablesPIDcontrolofupto20loops/system(upto
6loops/systemfortheGX10/GP10/GX20-1/GP20-1/
GM10-1). In addition to control loop monitoring and
thecontrolgroupscreenforconvenientoperation,
adjustmentusingthetuningscreenisavailable.
● Addingthe/PGoptiontotheGX/GP/GMmainunit
allows 99 patterns and 99 segments (1 pattern)
ofprogrampatternstobestoredinthemainunit.
Further,upto32timeeventsand32PVeventscan
besetforeachsegment.
● TheGX90UTcontroldatacanbeacquiredand
recordedintheGX/GP/GMmainunit.
PIDControlModuleSpecications
(Model: GX90UT)
Use
Controllingtemperature,owrate,pressure,etc.
AnalogInput
• Measurement types: DC voltage (DCV), standard
signal, type (TC), resistance temperature detector
(RTD), DI (LEVEL, no-voltage contact), DC current
(whenexternalshuntresistorisconnected)
•Numberofmeasurementpoints:2
•Scanperiod:Sameasthecontrolperiod
•Inputformat:Floatingunbalancedinput,isolation
betweenchannels
• Measuring range/accuracy:
Seethetablein“MeasuringRange/
Accuracy” (page 3).
• Burnout detection:
Upscale,downscale,andoffcan
bespecied(foreachchannel).
Detectableinputs:Thermocouple,resistance
temperature detector, standard signal
Detection condition:
Thermocouple:Detectioncurrent:approx.100nA,
superposed electric current system
RTD:Detectioncurrent:approx.100nA,superposed
electric current system
Standardsignal:Normal:withinmeasurementrange
Disconnection:basedontheburnout
criteria setting
Thecriteriaissetasapercentageofthespecied
spanwidth.
Lower limit: -20.0 to -5.0%
Upper limit: 105 to 120%
•Externalinputresistance:
DCvoltage,thermocouple:2kΩorless
RTD:
10Ωorlessperline(thesameresistanceforall
threelines)
•Inputbiascurrent:
±10nAorless(exceptwhen
burnoutdetectionisset)
•Measurementcurrent(RTD):Approx.1mA,approx.
1.6 mA
Input resistance:
10MΩormoreforthermocouple/DCvoltage(1V
range or lower)
About1MΩforDCvoltage(2Vrangeorhigher)/
standard signal
•Allowablesignalsourceresistance
2kΩorlessforthermocouple/DCvoltage(1Vrange
or less)
•Effectofsignalsourceresistance:
±10μV/1kΩorlessforthermocouple/DCvoltage(1
V range or less)
±0.15%/1kΩorlessforDCvoltage(2Vrangeor
higher)/standardsignal
•Effectofwiringresistance:
Fluctuationper10Ωchangeperline(the
sameresistanceforallthreelines)
RTD(100Ωtypeorhigher):±0.1°C/10Ω
RTD(50Ωtypeorlower):±1°C/10Ω
•Allowableinputvoltage:
Thermocouple,DCvoltage(1Vrangeorlower),
RTD, DI(contact input): ±10 VDC
DCvoltage(2Vrangeorhigher),DI(level):±60VDC
• Normal-mode rejection ratio: 40 dB or more
• Common mode rejection ratio: 120 dB or more