1-73
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
Description
Retransmission Output Operation
• If the output value is outside +105% to -5% of the reference channel’s set span, the
output is clipped at the boundaries of this span. (If the output value is outside the 0 to 22
mA range, the output is clipped at the boundaries of this range.)
• If the reference channel is a measurement channel or communication channel, when the
reference channel is +OVER, the output is clipped at 105% of the output channel’s set
span. When the reference channel is -OVER, the output is clipped at -5% of the set span.
Preset action
When the reference channel is a measurement channel
State Preset action
When retransmission output is off Preset action when stopped
When the module has been removed, measurement
channel is set to Skip, A/D error, calibration error, burnout
Preset action on error
When the reference channel is a communication channel
State Preset action
When retransmission output is off Preset action when stopped
When NaN is input, communication channel is off Preset action on error
When the reference channel is a math channel
State Preset action
When math is stopped Preset action when stopped
When retransmission output is off
When the math channel value is +OVER, -OVER, math
error, or when the math channel is off
Preset action on error
Measuring
Computing
Stopped
Retrans.
output
ON/OFF
Measurement
Calculation
Retrans.
output
Retrans.
output
Computing
On Off On
Preset action
when stopped
Previous value
Preset value (0)
Preset action when stopped
Previous value
Preset value (0)
When the reference channel is a measurement
channel or communication channel
When the reference channel is a math channel
Preset action on error also when ±OVER occurs
When OVER occurs: 105% of span
1.5ConfiguringAOChannels(Analoginputchannels)