SV-DA200 series AC servo drive Function codes
-143-
6.4.3 Digital input / output settings
P3.40
1
Travel limit switch shield
Setting range
Default
Unit
Available mode
02
1
-
P
S
T
This parameter is used to set whether the digital input configured as forward drive disabling
(0x001 or 0x101) and reverse drive disabling (0x002 or 0x102) is valid or not. If the function of the
travel limit switch needs to be shielded , this parameter can do the trick.
Setting value
Function
0
Travel limit switch is normal
[1]
Travel limit switch is disabled
2
Ultralimit fault
Note: When the travel limit switch is normal and the digital input configured as forward drive
disabling is active, the motor will stop immediately and cannot continue to run forward, but it is
able to receive the reverse running command.
P3.40
1
Data size
16bit
Data format
DEC
Modbus address
1680, 1681
CANopen address
0x2328, 0x00
P3.41
1
Emergency stop switch
shield
Setting range
Default
Unit
Available mode
01
1
-
P
S
T
This parameter is used to set whether digital input configured as EMG (0x016 or 0x116) is valid or
not. If the function of the emergency stop switch needs to be shielded, this parameter can do the
trick.
Setting value
Function
0
Emergency stop switch is normal
[1]
Emergency stop switch is disabled
If the digital input set as EMG is active, then Er10-4 will occur.
Note:
1. If Er10-4 occurs, the servo drive will stop at the stopping mode set by P4.30.
2. Clearance of Er10-4: Please ensure there is no danger, and then clear the alarm signal
(disable the digital input configured as EMG). After clearing the alarm displayed, it is necessary to
enable the servo drive again to operate the servo system.
P3.41
1
Data size
16bit
Data format
DEC
Modbus address
1682, 1683
CANopen address
0x2329, 0x00
P3.43
1
Digital input filter
Setting range
Default
Unit
Available mode
1800
1
0.125ms
P
S
T
This parameter is used to set the filter time of the digital input.
Note: The parameter works alone for 10 digital inputs.
P3.43
1
Data size
16bit
Data format
DEC
Modbus address
1686, 1687
CANopen address
0x232B, 0x00

Table of Contents

Other manuals for INVT SV-DA200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INVT SV-DA200 Series and is the answer not in the manual?

INVT SV-DA200 Series Specifications

General IconGeneral
BrandINVT
ModelSV-DA200 Series
CategoryServo Drives
LanguageEnglish

Related product manuals