SV-DA200 series AC servo drive Function codes
-91-
Generally, the system will set this parameter automatically after P0.00 is set correctly. In cases
where encoder disconnection fault is reported during power up when motor is connected
correctly, please check whether the drive supports motor encoder type, refer to chapter 1.1.3.
The naming of servo motor contains encoder type, refer to chapter 1.2.2.
Relation between encoder type and P0.01 setting value:
Motor nameplate
Encoder type*
2
2500-PPR standard incremental
17-bit single-turn absolute value
17-bit multi-turn absolute value *
3
23-bit multi-turn absolute value *
3
*
1
Different motors correspond to different types of encoders.
*
2
Refer to chapter 1.2.2 .
*
3
When the multi-turn encoders are used, it is necessary to change the battery when the drive is
power on to prevent losing absolute position. The standard battery is 2000mAh and the
replacement cycle is 1.5–2 years.
Forward rotation of motor *
1
Set the forward rotation of motor:
Anticlockwise is forward rotation
Clockwise is forward rotation
*
1
Definition of forward rotation of motor. The view angle faces shaft output direction of motor.