1-61
IM 04L51B01-01EN
Configuring the GX/GP and Viewing the Settings
1
Zone
Setup Item Selectable Range or Options Default Value
Lower 0 to 95% 0
Upper 5 to 100% 100
Lower,Upper
Set these values when you want to divide the waveform displays of channels into
separate zones so that waveforms do not overlap. Set the Lower and Upper positions as
percentages of the maximum display width. Set Lower to a value less than Upper, and set
the zone width (Upper – Lower) to be 5% or greater.
Scale
Setup Item Selectable Range or Options Default Value
Position GX20, GP20: Off, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10
GX10, GP10: Off, 1, 2, 3, 4, 5, 6
1
Division
1
4, 5, 6, 7, 8, 9, 10, 11, 12, C10 10
1 Appears when the Rage Type is set to Pulse.
Position
Set this to set the scale display position of the trend display. Set this to Off to not display
scales.
Division
Set the number of divisions to make with the main scale marks.
C10: The scale is equally divided into 10 sections by main scale marks, and scale values are
indicated at 0, 30, 50, 70, and 100% positions.
For display examples, see the scale settings on page 1-40 in section 1.2.3, “Setting the
Display”.
Bar graph
Setup Item Selectable Range or Options Default Value
Base position Lower, Center, Upper Lower
Division
1
4, 5, 6, 7, 8, 9, 10, 11, 12 10
1 Appears when the Rage Type is set to Pulse.
Base position
Set the bar graph base position. This setting is applied on the bar graph display and when
you are displaying the current value on the scale as a bar graph on the trend displays.
Division
Set the number of divisions to make with the main scale marks.
For display examples, see the bar graph settings on page 1-40 in section 1.2.3, “Setting the
Display”.
1.3ConfiguringDIChannels(Digitalinputchannels)