1. Description of easyE4 control relay
1.10 Engineering
1.10 Engineering
The easyE4 series makes it possible to combine multiple voltage variants. Each base
device can be wired with up to 11 EASY-E4-...-...E1(P) expansions with different
power supplies.
1.10.1 Length of Signal input cables
1.10.1.1 Digital inputs
Severe interference can cause a signal 1 on the inputs without a proper signal being
applied.
Therefore, observe the following maximum cable lengths without additional circuitry:
Basic device Digital inputs Qty. Max. cable length in m
EASY-E4-UC-12…
EASY-E4-DC-12…
24 V DC
8
Of which can be used
100 (unshielded)
4 (I5, I6, I7, I8)
as analog inputs
30 screened
4 (I1, I2, I3, I4)
as frequency counter or rapid
counter inputs
20 (screened)
2 (I1 + I2, I3 + I4)
as incremental counter
20 (screened)
EASY-E4-UC-12…
12 V DC
8

100 (unshielded)
EASY-E4-UC-12…
24 V AC
8

40 (unshielded)
EASY-E4-AC-12…
115/230 V AC
8
(I1 - I6)
40 (unshielded)
(I7, I8)
100 (unshielded)

I/O expansion Digital inputs Qty. Cable length in m
EASY-E4-DC-16TE1(P)
EASY-E4-UC-16RE1(P)
24 V DC
8
100 (unshielded)
EASY-E4-DC-8TE1(P)
EASY-E4-UC-8RE1(P
4
100 (unshielded)
EASY-E4-UC-16RE1(P)
12 V DC
8
100 (unshielded)
EASY-E4-UC-8RE1(P) 4
100 (unshielded)
EASY-E4-UC-16RE1(P)
24 V AC
8
40 (unshielded)
EASY-E4-UC-8RE1(P) 4
40 (unshielded)
EASY-E4-AC-16RE1(P)
115/230 V AC

8
40 (unshielded)
EASY-E4-AC-8RE1(P)
4 40 (unshielded)
easyE402/24 MN050009ENEaton.com