6.3.2 Error conguraon
The errors can be divided into two types:
•
Errors with predened error type
•
Errors with congurable error type
Especially crical errors are permanently set to the "Fault" error type in order to protect inver-
ter and motor from damages.
In case of errors with congurable error type, the default seng can be changed in considera-
on of safety aspects and the operaonal performance. The selecon "No response [0]" is,
however, only available for minor errors.
The "Error codes" table lists the error type for each error. If the error type can be congured
by the user, the "adjustable in" column displays the corresponding parameter. ^ 639
6.3.3 Error reset
If the error condion is not acve anymore, there are several opons to reset an acve error
and thus leave the error state again:
•
Via the keypad key . 4Error reset with keypad ^ 634
•
Via the trigger assigned to the Reset fault"
funcon. 4Reset error ^ 570
•
Via the buon in the »EASY Starter« ("Diagnoscs" tab).
•
In the default seng of 0x400E:008 (P505.08) via bit 7 in the mappable data word Net-
WordIN1 0x4008:001 (P590.01).
•
Via bit 7 in the mappable CiA 402 control word 0x6040.
•
Via bit 2 in the mappable AC Drive control word 0x400B:001 (P592.01).
•
Via bit 11 in the mappable LECOM control word 0x400B:002 (P592.02).
Notes:
•
Certain errors can only be reset by mains switching.
•
Certain errors (e. g. earth fault or short circuit of the motor phases) may cause a blocking
me. In this case, the error can be reset only aer the blocking me has elapsed. An acve
blocking me is displayed via bit 14 in the inverter status word 0x2831.
The "Error codes" table gives the blocking me (if available) for each error. This table also
shows whether mains switching is required for the error reset. ^ 639
6.3.4 Keypad error messages
If an error is pending, the keypad shows the following informaon:
Keypad display Meaning
MAN AUTO SETLOC REM
Warn.DC Bus UV
O 1 W 3 2 2 1
•
Faults (F) and trouble (T) are displayed con-
nuously.
•
Warnings (W) are only displayed every 2 sec-
onds for a short me.
①
Error text
②
Error type:
F Fault
T Trouble
W Warning
③
Error code (hexadecimal)
4Error codes ^ 639
4Error reset with keypad ^ 634
MAN AUTO SETLOC REM
AI1 fault
Restart Pending
O O F 7 O 8 1
Aer a disturbance, a restart is possible if the error condion is not acve anymore. The keypad
shows this by the "Restart Pending" note. The note is displayed in a 1-second interval alternang
with the error text.
4Timeout für fault reacon ^ 483
Diagnoscs and fault eliminaon
Error handling
Keypad error messages