8.4.4.6 Flying restart controller
For a quick commissioning, the calculaons and sengs are made automacally during the
opmisaon.
Precondions
The ying restart controller is only eecve in the following motor control types:
•
V/f characterisc control (VFC open loop)
•
Sensorless control (SL PSM)
•
Sensorless vector control (SLVC)
Details
The following parameter is only relevant for the ying restart circuit if an asynchronous motor
is controlled. In case of a sensorless control of a synchronous motor (SL-PSM) the parameter
has no meaning.
Parameter Name / value range / [default seng] Info
0x2BA1:003
(P718.03)
Flying restart circuit: Restart me
(Flying restart: Restart me)
1 ... [5911]* ... 60000 ms
* Default seng depending on the size.
Integraon me for controlling the ying restart circuit.
8.4.4.7 SLVC controller
For a quick commissioning, the calculaons and sengs are made automacally during the
opmisaon.
Precondions
The SLVC controller is only eecve in the motor control type "Sensorless vector control
(SLVC)".
Parameter Name / value range / [default seng] Info
0x2B40:001 Gain
0.0000 ... [0.2686]* ... 1000.0000 Hz/A
* Default seng depending on the size.
Gain of the SLVC-Q controller.
0x2B40:002 Reset me
1.0 ... [2.3]* ... 2000.0 ms
* Default seng depending on the size.
Reset me of the SLVC-Q controller.
Motor control
Opmisaon of the control loops
Motor controller sengs
205