14.3.1 Priority of the setpoint sources
Since only one setpoint source can be acve at a me, the following priories apply:
Flexible I/O conguraon or keypad control acve
0x2631:037 (P400.37) = FALSE
Network control acve
0x2631:017 (P400.17) = FALSE
0x2631:037 (P400.37) = TRUE
Prio 1: Funcons for setpoint change-over
The priority of the funcons results from the assigned triggers (in the
order of the selecon list):
1.
Constant TRUE [1]
2.
Digital input 1 [11]
3.
Digital input 2 [12]
4.
Digital input 3 [13]
5.
...
Prio 1: Setpoint source selected via network control word
4General network sengs ^ 227
Prio 2: Set standard setpoint source
•
0x2860:001 (P201.01): Frequency control: Default setpoint source
•
0x2860:002 (P201.02): PID control: Default setpoint source
4Selecon of setpoint source ^ 148
Prio 2: Set standard setpoint source
•
0x2860:001 (P201.01): Frequency control: Default setpoint source
•
0x2860:002 (P201.02): PID control: Default setpoint source
4Selecon of setpoint source ^ 148
Example of allocang priority
Parameter Name Seng for this example
0x2631:014 (P400.14) Acvate AI1 setpoint Digital input 5 [15]
0x2631:016 (P400.16) Acvate keypad setpoint Digital input 4 [14]
Digital input 4 Digital input 5 Acve setpoint source
FALSE FALSE Standard setpoint source set in 0x2860:001 (P201.01)
FALSE TRUE Analog input 1
TRUE FALSE keypad
TRUE TRUE Keypad (since "Digital input 4" trigger is higher in the selecon list than "Digital input 5" trigger)
14.3.2 Analog input setpoint source
The following funcons are used to select analog input 1 or analog input 2 as setpoint source.
Precondions
A setpoint change-over to the respecve analog input is only eected if no setpoint source
with a higher priority has been selected. 4Priority of the setpoint sources ^ 548
Parameter Name / value range / [default seng] Info
0x2631:014
(P400.14)
Funcon list: Acvate AI1 setpoint
(Funcon list: Setp: AI1)
•
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Acvate AI1 setpoint" funcon.
Trigger = TRUE: analog input 1 is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no acon / deacvate funcon again.
4Analog input 1 ^ 597
0 Not connected
Flexible I/O conguraon
Setpoint change-over
Priority of the setpoint sources
548