Read the drive speed via Modbus
The drive speed can be read out via the Modbus register 42002, see Data mapping. For read-
ing a single register or several connected register blocks, the funcon code 3 is used, see
Funcon codes.
Example of an inverter with the node address 1:
Request frame by the master
Slave address Funcon code Data Checksum (CRC)
Register address Number of words
0x01 0x03 0x07 0xD1 0x00 0x01 0xD5 0x47
Response message from the inverter
Slave address Funcon code Data Checksum (CRC)
Read bytes Frequency (0.01)
0x01 0x03 0x02 0x04 0xD1 0x7A 0xD8
The drive rotates with a frequency of 12.33 Hz.
Parameter Name / value range / [default seng] Info
0x2631:037
(P400.37)
Funcon list: Acvate network control
(Funcon list: Network control)
•
For further possible sengs, see parameter
0x2631:001 (P400.01). ^ 532
Assignment of a trigger for the "Acvate network control" funcon.
Trigger = TRUE: Acvate network control.
Trigger = FALSE: No acon / deacvate network control again.
0 Not connected
114 Network control acve (from version 02.00) TRUE if the network control is requested via bit 5 of the AC drive control
word 0x400B:001 (P592.01). Otherwise FALSE.
Notes:
•
Set this selecon if the network control is to be acvated via bit 5 of
the AC drive control word.
•
The AC drive control word can be used with any communicaon pro-
tocol.
4AC Drive Prole ^ 248
9.8.9 Restart communicaon
Parameter Name / value range / [default seng] Info
0x23B0
(P508.00)
Modbus TCP communicaon
(MBTCP comm.)
•
From version 04.00
Restart / stop communicaon
0 No acon/no error Only status feedback.
1 Restart with current values Restart communicaon in order that changed sengs of the interface
conguraon become eecve.
2 Restart with default values Restart communicaon with the standard values.
5 Stop network communicaon Stop communicaon.
10 In progress Only status feedback
11 Acon cancelled
12 Error
9.8.10 Baud rate seng
Parameter Name / value range / [default seng] Info
0x23B4:001
(P512.01)
Port sengs: Port 1
(Port sengs: Port 1)
•
From version 04.00
Set baud rate for the port 1.
0 Auto-Negoaon
1 10 Mbps
2 100 Mbps
5 10 Mbps/Half Duplex
6 10 Mbps/Full Duplex
7 100 Mbps/Half Duplex
8 100 Mbps/Full Duplex
Conguring the network
Modbus TCP
Restart communicaon