Parameter Name / value range / [default seng] Info
0x2631:001
(P400.01)
Funcon list: Enable inverter
(Funcon list: Enable inverter)
•
Seng can only be changed if the inverter is inhibi-
ted.
Assignment of a trigger for the "Enable inverter" funcon.
Trigger = TRUE: The inverter is enabled (unless there is another cause for
inverter disable).
Trigger = FALSE: The inverter is disabled.
Notes:
•
This funcon must be set to TRUE to start the motor. Either via an
assigned digital input or by default seng "Constant TRUE [1]".
•
Changing to the inhibited state causes an immediate stop of the
motor, regardless of the stop method set in 0x2838:003 (P203.03).
The motor becomes torqueless and coasts down as a funcon of the
mass inera of the machine.
•
The cause(s) that are acve for the disabled state are shown in
0x282A:001 (P126.01).
0 Not connected No trigger assigned (trigger is constantly FALSE).
1 Constant TRUE Trigger is constantly TRUE.
11 Digital input 1 State of X3/DI1, taking an inversion set in 0x2632:001 (P411.01) into
consideraon.
12 Digital input 2 State of X3/DI2, taking an inversion set in 0x2632:002 (P411.02) into
consideraon.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (P411.03) into
consideraon.
14 Digital input 4 State of X3/DI4, taking an inversion set in 0x2632:004 (P411.04) into
consideraon.
15 Digital input 5 State of X3/DI5, taking an inversion set in 0x2632:005 (P411.05) into
consideraon.
16 Digital input 6 State of X3/DI6, taking an inversion set in 0x2632:006 (P411.06) into
consideraon.
Digital input 6 is only available in the Control Unit (CU) with applicaon
I/O.
17 Digital input 7 State of X3/DI7, taking an inversion set in 0x2632:007 (P411.07) into
consideraon.
Digital input 7 is only available in the Control Unit (CU) with applicaon
I/O.
50 Running TRUE if inverter and start are enabled and output frequency > 0.2 Hz.
Otherwise FALSE.
51 Ready for operaon TRUE if inverter is ready for operaon (no error acve, no STO acve and
DC-bus voltage ok). Otherwise FALSE.
53 Stop acve TRUE if inverter is enabled and motor is not started and output fre-
quency = 0.
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A warning has no impact on the operang status of the inverter.
•
A warning is reset automacally if the cause has been eliminated.
59 Device fault acve TRUE if a fault is acve. Otherwise FALSE.
•
In the event of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
•
Excepon: In case of a serious fault, the inverter is disabled immedi-
ately. The motor becomes torqueless (coasts).
•
The error state will be le automacally if the error condion is not
acve anymore.
•
The restart behaviour aer trouble can be congured. 4Automac
restart ^ 484
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for tempera-
ture monitoring. Otherwise FALSE.
•
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
•
Seng of the warning threshold in 0x2D84:002.
69 Rotaonal direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
•
Seng Frequency thresholdin 0x4005 (P412.00).
4Frequency threshold for "Frequency threshold exceeded" trigger ^ 593
Flexible I/O conguraon
Start / stop motor
532