4.2.2.2 Fusing and terminal data
Fuse data
Inverter I55AE125B
I55AE137B
I55AE125D
I55AE137D
I55AE155B
I55AE175B
I55AE155D
I55AE175D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 10 10 16 16
Circuit breaker
Characteriscs B
Max. rated current A 10 10 16 16
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B - ≥ 30 mA, type B
Fuse data
Inverter I55AE211B
I55AE215B
I55AE222B
I55AE211D
I55AE215D
I55AE222D
Cable installaon in compliance with EN 60204-1
Installaon method B2
operaon without mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
operaon with mains choke
Fuse
Characteriscs gG/gL or gRL
Max. rated current A 25 25
Circuit breaker
Characteriscs B
Max. rated current A 25 25
Earth-leakage circuit breaker
1-phase mains connecon ≥ 30 mA, type A or B
3-phase mains connecon - ≥ 30 mA, type B
Electrical installaon
Mains connecon
1-phase mains connecon 230/240 V
34

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals