EasyManuals Logo

Lenze i55AE155F User Manual

Lenze i55AE155F
702 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #371 background image
9.9.6 Data mapping
The process data are used to control the inverter.
The process data is transmied cyclically between the IO-Controller and the IO-Devices parc-
ipang at the PROFINET:
The available 27 network registers ("slots") serve to maximally exchange 16 process data
words (data types 8-bit or 16-bit) or 8 process data double words (data type 32-bit) for
each direcon.
Output data direcon: From IO-Controller to IO-Device.
Input data direcon: From IO-Device to IO-Controller.
Data mapping is used to dene which process data are exchanged cyclically between IO-Con-
troller andIO-Device.
Details
If the inverter is known in the PROFINET network as node and the IO-Controller connects
to the IO-Device for the rst me, the mapping objects are automacally transferred to
the IO device, i. e. to the inverter.
Internal mapping of the process output data is set in 0x24E0:001 ... 0x24E0:016.
Internal mapping of the process input data is set in 0x24E1:001 ... 0x24E1:016.
All subsequent changes in the objects 0x24E1 and 0x24E1 can cause PROFINET
alarms according to the deviaon of the automacally set conguraons.
Conguring the network
PROFINET
Data mapping
371

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals