9.5.10 Restart communicaon
The following parameter can be used to restart communicaon.
Details
A restart of communicaon is required aer changes of the interface conguraon (e. g. node
address and baud rate) in order that the changed sengs become eecve.
For restarng communicaon, there are two opons:
a)
Switch inverter o and on again.
b)
Set the selecon = "Restart with current values [1]" in 0x2320 (P508.00).
Parameter Name / value range / [default seng] Info
0x2320
(P508.00)
Modbus communicaon
(Modbus comm.)
1 = restart communicaon in order that changed sengs of the interface
conguraon become eecve.
0 No acon/no error
1 Restart with current values
9.5.11 Response me seng
Dene a minimum me delay between the recepon of a valid Modbus message and the
response of the inverter.
Especially at higher baud rates, dening a minimum me delay ensures the data exchange
between transmier (Modbus master) and receiver (e. g. inverter).
Parameter Name / value range / [default seng] Info
0x2321:004
(P510.04)
Modbus sengs: Minimum response me
(Modbus se.: Min. resp. me)
0 ... [0] ... 1000 ms
Conguring the network
Modbus RTU
Response me seng
291