15 Technical data
15.1 Standards and operang condions
15.1.1 Conformies/approvals
Conformity
CE 2014/35/EU Low-Voltage Direcve
2014/30/EU EMC Direcve (reference: CE-typical drive system)
EAC TR TC 004/2011 Eurasian conformity: safety of low voltage equipment
TP TC 020/2011 Eurasian conformity: electromagnec compability of technical
means
RoHS 2 2011/65/EU Restricons for the use of specic hazardous materials in electric
and electronic devices
Approval
UL UL 61800-5-1 for USA and Canada (requirements of the CSA 22.2 No. 274)
File No. E132659
15.1.2 Protecon of persons and device protecon
Enclosure
IP20 EN 60529
Type 1 NEMA 250 Protecon against contact
Open type only in UL-approved systems
Insulaon resistance
Overvoltage category III EN 61800-5-1 0 … 2000 m a.m.s.l.
Overvoltage category II above 2000 m a.m.s.l.
Control circuit isolaon
Safe mains isolaon by double/reinforced
insulaon
EN 61800-5-1
Protecve measures against
Short circuit
earth fault Earth fault strength depends on the operang status
Overvoltage
Motor stalling
Leakage current
> 3.5 mA AC, > 10 mA DC EN 61800-5-1 Observe regulaons and safety instrucons!
Starng current
≤ 3 x rated mains current
15.1.3 EMC data
Actuaon on public supply systems
Implement measures to limit the radio interfer-
ence to be expected:
The machine or plant manufacturer is responsible for compliance
with the requirements for the machine/plant!
< 1 kW: with mains choke EN 61000-3-2
> 1 kW at mains current ≤ 16 A: without addi-
onal measures
Mains current > 16 A: with mains choke or
mains lter, with dimensioning for rated
power. Rsce ≥ 120 is to be met.
EN 61000-3-12 RSCE: short-circuit power rao at the connecon point of the
machine/plant to the public network.
Noise emission
Category C1 EN 61800-3 Type-dependent, for motor cable lengths see rated data
Category C2
Noise immunity
Meets requirement in compliance with EN 61800-3
Technical data
EMC data
622