Parameter Name / value range / [default seng] Info
0x2859:005
(P515.05)
PROFIBUS monitoring: Invalid process data
(PROFIBUS monit.: Inval. proc.data)
•
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response triggered by the recepon of invalid process
data.
•
If the master changes to the "Stop" state, no cyclic process data are
sent to the inverter (slave) anymore; the length of the process data
then is 0.
Associated error code:
•
33171 | 0x8193 - Network: invalid cyclic process data
2 Trouble
9.6.6 LED status displays
Informaon about the PROFIBUS status can be obtained quickly via the "NS" and "NE" LED
displays on the front of the inverter.
The meaning can be seen from the table below.
LED "NS" (green) LED "NE" (red) Status/meaning
o o No supply voltage available, network deacvated, not inialised, or rmware download acve.
on
Connected with master, control running, "Data Exchange" state acve.
Blinking
Not connected, control stopped, or no data exchange.
Blinking Blinking
Watchdog monitoring me elapsed.
Any
Flashing
PROFIBUS parameterisaon error.
Flashing 2 x
PROFIBUS conguraon error.
o on
Invalid staon address set or non-correctable error.
9.6.7 Diagnoscs
The following parameters serve to diagnose the communicaon acvies between the inver-
ter and the PROFIBUS network.
Parameter Name / value range / [default seng] Info
0x2344:001
(P512.01)
PROFIBUS Conguraon: Extended diagnosc bit
(PROFIBUS Cong.: Ext. diag. bit)
1 = set external diagnosc bit ("Diag Bit").
•
The diagnosc bit is sent to the master where it is evaluated sepa-
rately.
0 Delete
1 Set
0x2348:001
(P516.01)
PROFIBUS Status: Bus status
(PROFIBUS Status: Bus status)
•
Read only
Display of the current DP state machine state (DP-STATE).
0 WAIT_PRM Aer the run-up, the inverter (slave) is waing for parameter data
(CHK_PRM) from the master. All other frame types are not processed.
Exchanging user data with the master is not possible yet.
1 WAIT_CFG The inverter (slave) is waing for conguraon data (CHK_CFG) from the
master that dene the structure of the cyclic frames.
2 DATA_EXCH Parameter and conguraon data have been received and accepted by
the inverter (slave). The inverter is in the "Data Exchange" state. It is now
possible to exchange user data with the master.
0x234A:001
(P580.01)
PROFIBUS stascs: Data cycles per second
(PROFIBUS counter: Data cycles/sec.)
•
Read only
Display of the data cycles per second.
0x234A:002
(P580.02)
PROFIBUS stascs: Parameterizaon events
(PROFIBUS counter: PRM events)
•
Read only
Display of the number of parameterisaon events.
0x234A:003
(P580.03)
PROFIBUS stascs: Conguraon events
(PROFIBUS counter: CFG events)
•
Read only
Display of the number of conguraon events.
0x234A:004
(P580.04)
PROFIBUS stascs: Diagnoscs events
(PROFIBUS counter: DIAG events)
•
Read only
Display of the number of diagnosc telegrams sent.
Conguring the network
PROFIBUS
LED status displays
298