8.7.6 Motor speed monitoring
This funcon monitors the motor speed during operaon.
Precondions
In order to detect the current motor speed, the inverter must be enabled and the motor
must rotate.
For an exact monitoring, rated motor speed 0x2C01:004 (P320.04) and rated motor fre-
quency 0x2C01:005 (P320.05) must be set correctly.
Details
If the motor speed reaches the threshold set in 0x2D44:001 (P350.01), the response set in
0x2D44:002 (P350.02) takes place.
With the seng 0x2D44:002 (P350.02) = "No response [0]", the monitoring funcon is
deacvated.
Parameter Name / value range / [default seng] Info
0x2D44:001
(P350.01)
Overspeed monitoring: Threshold
(Overspeed monit.: Threshold)
50 ... [8000] ... 50000 rpm
Warning/error threshold for motor speed monitoring.
If the motor speed reaches the threshold set, the response selected in
0x2D44:002 (P350.02) is eected.
The parameter is calculated and set in the course of the automac
idencaon of the motor.
The parameter can also be set and thus overwrien by selecng a
motor in the engineering tool from the "motor catalog" or calibrang
the motor.
4Opmisaon of the control loops ^ 193
0x2D44:002
(P350.02)
Overspeed monitoring: Response
(Overspeed monit.: Response)
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of the response to the triggering of motor speed monitoring.
Associated error code:
65286 | 0xFF06 - Motor overspeed
3 Fault
8.7.7 Motor torque monitoring
This funcon monitors the motor torque during operaon.
Precondions
The motor torque monitoring can only be used for the following motor control types with
speed controller:
Servo control (SC ASM)
Sensorless control (SL PSM)
Sensorless vector control (SLVC)
Details
This funcon sets the internal status signal "Torque limit reached [79]" = TRUE if the maximum
possible torque has been reached.
The status signal is set irrespecve of the response 0x2D67:001 (P329.01) and delay me
0x2D67:002 (P329.02) set for this monitoring.
The user can use the status signal to acvate certain funcons. 4Flexible I/O congura-
on ^ 525
The status signal also serves to set a digital output or a bit of the NetWordOUT1 status
word. 4
Conguraon of digital outputs ^ 603
Parameter Name / value range / [default seng] Info
0x2D67:001
(P329.01)
Maximum torque monitoring: Response
(MaxTrq.Monitor: Response)
From version 02.00
For further possible sengs, see parameter
0x2D45:001 (P310.01). ^ 223
Selecon of response to reaching the maximum possible torque.
The selected response takes place if the status signal "Torque limit
reached [79]" = TRUE and the deceleraon me set in 0x2D67:002
(P329.02) has elapsed.
Associated error code:
33553 | 0x8311 - Torque limit reached
0 No response
Motor control
Motor protecon
Motor speed monitoring
224

Table of Contents

Other manuals for Lenze i55AE155F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenze i55AE155F and is the answer not in the manual?

Lenze i55AE155F Specifications

General IconGeneral
BrandLenze
Modeli55AE155F
CategoryInverter
LanguageEnglish

Related product manuals